1. Single-phase power cords for portable electric machinery and handheld power tools must use three-core flexible rubber cables, while three-phase power cords must use four-core rubber cables; during wiring, the cable sheath must extend into the equipment's terminal box and be securely fastened.
2. Before using power tools, the following items must be inspected:
(1) The casing and handle are free from cracks and damage;
(2) The protective grounding wire or neutral wire is connected correctly and securely;
(3) The cable or flexible cord is intact;
(4) The plug is intact;
(5) The switch operates normally and smoothly, with no defects;
(6) Electrical protection devices are intact;
(7) Mechanical protective devices are intact;
(8) Rotating parts move freely.
3. The insulation resistance of power tools must be measured periodically using a 500V megohmmeter; if the insulation resistance between live parts and the casing falls below 2 MΩ, repairs must be performed.
4. After the electrical components of a power tool have been repaired, insulation resistance measurement and a dielectric withstand voltage test must be conducted; the test voltage shall be 380V, and the test duration shall be 1 minute.
5. Electrical circuits supplying electric machinery and tools must be equipped with dedicated switches or sockets and fitted with a residual current device (RCD); metal casings must be grounded; connecting multiple pieces of equipment to a single switch is strictly prohibited.
6. For current-operated residual current devices, the rated residual operating current must not exceed 30 mA, and the operating time must not exceed 0.1 seconds; for voltage-operated residual current devices, the rated residual operating voltage must not exceed 36V.
7. The operating switch for electric tools must be positioned within easy reach of the operator. The power supply switch must be turned off during breaks, at the end of the shift, or in the event of a sudden power outage during work.
8. When using portable or mobile power tools, operators must wear insulating gloves or stand on an insulating mat; when moving the tool, one must not carry it by the power cord or by its rotating parts. 9. When using Class III insulated power tools in damp or acidic environments, or inside metal containers, reliable insulation measures must be implemented and a dedicated monitor assigned. The power tool's switch must be positioned within easy reach of the monitor.
10. The magnetic base of a magnetic-base electric drill must be flat, clean, and free of rust; when performing side or overhead drilling, measures must be taken to prevent the drill unit from falling in the event of a power failure.
11. When using an electric wrench, securely position the reaction torque support point and ensure the socket is firmly engaged with the nut before starting the tool.